Standpipe Systems
BC 1704.22
1704.22 Standpipe system special inspection. New and altered standpipe systems shall be inspected in accordance with Sections 905 and 1704.22.1. The permit holder responsible for the standpipe work shall perform all required acceptance tests, and complete and sign the appropriate contractor’s material and test certifications. The special inspector shall witness all required tests, verify that installation of all materials, fittings, hangers, assemblies and signage are in accordance with the approved construction documents, that painting of the standpipe system required by Section 905.11 of this code has been performed and that the contractor has transmitted required maintenance literature and instruction to the owner. The special inspector shall verify that the material and test certification forms have been transmitted to the Fire Department and the Department of Buildings‡.
Exception: The special inspector need not witness the hydrostatic pressure test shall not be required when such test is witnessed by the department.
Special Inspection: | Fire Standpipe Systems |
Code Section(s): | BC 1704.22 |
Minimum Qualifications: | Primary Inspector or Inspection Supervisor.
|
Supplemental Inspector (Alternative 1)
|
|
Supplemental Inspector (Alternative 2)
|
Inspection Task: | Inspection Interval (Continuous/Peri odic) | NYC Construction Code Reference Section | Reference Standard (e.g. ASTM X1234) | Baseline Document (Approved plans, Shop Drawings, Manufacturer’s Instructions, etc.) | Comments (e.g. needs test performed by Approved Testing Agency) |
1. Check for compliance with DOB approved plans. | Periodic. | BC 1704.22
BC 905.1 FC 901.6.1 |
• DOB approved plans. • PE/RA of record approved equipment and material submittals. | ||
2. Inspect and verify that the installations of all materials, fittings, hangers, assemblies and signage, complies with the installation standards. | Periodic – during the erection of piping and prior to concealment. | BC 1704.22 | • PE/RA of record approved equipment and material submittals. | ||
3. Inspect and record hydrostatic test results. | Periodic- At completion of installation before sign off. | BC 1704.22
BC 905.1 BC Q105 FC 901.5.6.1 |
• DOB approved plans.
• PE/RA of record approved equipment and material submittals. |
• Witness hydrostatic test,pressurized to 200 psi or 50 psi above the maximum operating pressure for 2 hours without loss of pressure. Test shall be completed for each zone.
• Transmit all required forms and test results to the Fire Department and the Department of Buildings. |
|
4. Inspect and record flow test results. | Periodic- At completion of installation before sign off. | BC 1704.22
BC 905.1 BC Q105 FC 901.5.6.1 |
NFPA 14, Chapter 11.5.1 | • DOB approved plans.
• PE/RA of record approved equipment and material submittals. |
• Witness flow test at the most remote hose outlets in each pressure zone. The maximum flow shall be 250 gpm per hose outlet at each test manifold with a pressure of 65 psi.
• Transmit all required forms and test results to the Fire Department adn the Department of Buildings. |
5. Reports & Filing | Immediately after inspection and test is conducted and passed. | BC 905.1
BC Q105 |
• DOB approved plans.
• PE/RA of record approved equipment and material submittals including a detail of procedures, methods to be used adn items subject to testing. |
• Complete report must include identification of all devices by manufacturer, nameplate data, design values, measured values and identification tag.
• A copy of the final report and each inspection shall be filed with the department and Fire Commissioner. • A record of inspections and test shall be maintained on the premises by the owner for at least two years. |
|
6. Re-Acceptance Testing | Conducted after any modifications to the system or physical changes to the building that may affect performance. | FC 901.6.1
BC 905.1 BC Q105 |
NFPA 25, Chapter 6 | • DOB approved plans.
• Previous inspection and testing report. • PE/RA of record approved equipment and material submittals including a detail of procedures, methods to be used and items subject to testing. |
• Perform same inspection and testing as outlined above to confirm performance of existing system. |