Fire Alarm Systems Test
When FDNY inspection not required
Special Inspection: | Fire Alarm Systems Test |
Code Section(s): | BC 907 |
Minimum Qualifications: | Primary Inspector or Inspection Supervisor.
|
Supplemental Inspector (Alternative 1)
|
|
Supplemental Inspector (Alternative 2)
|
Inspection Task: | Inspection Interval (Continuous/Peri odic) | NYC Construction Code Reference Section | Reference Standard (e.g. ASTM X1234) | Baseline Document (Approved plans, Shop Drawings, Manufacturer’s Instructions, etc.) | Comments (e.g. needs test performed by Approved Testing Agency) |
1. Check for compliance with DOB approved plans. | Periodic. | BC 907.16 | • DOB approved plans. • PE/RA of record approved equipment and material submittals. | • Note: A special inspection is required for the fire alarm system when a FDNY inspection is not required. | |
2. Perform visual inspections and verify that the installations of all materials, fittings, hangers, assemblies, and signage complies with the installation standards. | Periodic – during the erection of piping and prior to concealment. | BC 907.16 | NFPA 72 – Chapter 10 | • PE/RA of record approved equipment and material submittals. | |
3. Complete performance testing and verification. | Periodic- At completion of installation before sign off. | BC 907.16 | NFPA 72- Chapter 10.4 | • DOB approved plans.
• PE/RA of record approved equipment and material submittals. |
• All new systems shall be inspected and tested in accordance with NFPA 72- Chapter 10.
• Transmit all required forms and test results to the Fire Department and the Department of Buildings. |
4. Reports and Filing | Immediately after inspection and test is conducted and passed. | BC 907.16 | NFPA 72- Chapter 10.6 | • DOB approved plans.
• PE/RA of record approved equipment and material submittals including a detail of procedures, methods to be used and items subject to testing. |
• Complete report must include identification of all devices by manufacturer, nameplate data, design values, measured values and identification tag.
• A record of inspections and test shall be maintained until next test for one year thereafter. |
5. Re-Acceptance Testing. | Conducted after any modifications to the system or physical changes to the fire alarm system infrastructure. | BC 907.16 | NFPA 72- Chapter 10.4.1.2 | • DOB approved plans.
• PE/RA of record approved equipment and material submittals including a detail of procedures, methods to be used and items subject to testing. |
• Perform reacceptance testing in accordance with NFPA 72- Chapter 10.4.1.2. |