Fire Alarm Systems Test
When FDNY inspection not required
| Special Inspection: | Fire Alarm Systems Test | 
| Code Section(s): | BC 907 | 
| Minimum Qualifications: | Primary Inspector or Inspection Supervisor. 
  | 
Supplemental Inspector (Alternative 1) 
  | 
|
Supplemental Inspector (Alternative 2)
  | 
| Inspection Task: | Inspection Interval (Continuous/Peri odic) | NYC Construction Code Reference Section | Reference Standard (e.g. ASTM X1234) | Baseline Document (Approved plans, Shop Drawings, Manufacturer’s Instructions, etc.) | Comments (e.g. needs test performed by Approved Testing Agency) | 
| 1. Check for compliance with DOB approved plans. | Periodic. | BC 907.16 | • DOB approved plans. • PE/RA of record approved equipment and material submittals. | • Note: A special inspection is required for the fire alarm system when a FDNY inspection is not required. | |
| 2. Perform visual inspections and verify that the installations of all materials, fittings, hangers, assemblies, and signage complies with the installation standards. | Periodic – during the erection of piping and prior to concealment. | BC 907.16 | NFPA 72 – Chapter 10 | • PE/RA of record approved equipment and material submittals. | |
| 3. Complete performance testing and verification. | Periodic- At completion of installation before sign off. | BC 907.16 | NFPA 72- Chapter 10.4 | • DOB approved plans.
 • PE/RA of record approved equipment and material submittals.  | 
• All new systems shall be inspected and tested in accordance with NFPA 72- Chapter 10.
 • Transmit all required forms and test results to the Fire Department and the Department of Buildings.  | 
| 4. Reports and Filing | Immediately after inspection and test is conducted and passed. | BC 907.16 | NFPA 72- Chapter 10.6 | • DOB approved plans.
 • PE/RA of record approved equipment and material submittals including a detail of procedures, methods to be used and items subject to testing.  | 
• Complete report must include identification of all devices by manufacturer, nameplate data, design values, measured values and identification tag.
 • A record of inspections and test shall be maintained until next test for one year thereafter.  | 
| 5. Re-Acceptance Testing. | Conducted after any modifications to the system or physical changes to the fire alarm system infrastructure. | BC 907.16 | NFPA 72- Chapter 10.4.1.2 | • DOB approved plans.
 • PE/RA of record approved equipment and material submittals including a detail of procedures, methods to be used and items subject to testing.  | 
• Perform reacceptance testing in accordance with NFPA 72- Chapter 10.4.1.2. | 
        